Foundation course · Malaysian home electrical installations

Electrical 101

From V = I × R to what each box in your distribution board does, surge protection, protective devices, cable sizing and earthing. The order follows years 1–3 of an Electrical Engineering degree, focused on what you meet in your own home.

Circuit TheoryAC CircuitsPower SystemsElectrical Installation DesignProtectionMeasurement & Instrumentation
Module 01 · Circuit Theory

Voltage, current, resistance

After this module: you can use Ohm's Law and understand why a cable has resistance.

A water pipe is the easiest way to picture it:

QuantitySymbolUnitWater-pipe analogy
Voltage (potential difference)Vvolt (V)Water pressure in the pipe
CurrentIampere (A)How much water flows per second
ResistanceRohm (Ω)A narrow or partly blocked pipe
PowerPwatt (W)The work the water does per second

Ohm's Law

V = I × R → I = V ÷ R · R = V ÷ I

More pressure pushes more water through. A narrower pipe lets less water through.

Resistance of a cable

A cable has a small resistance of its own. It depends on three things: the material (copper or aluminium), the length, and the cross-sectional area (mm²).

R = ρ × L ÷ A ρ copper ≈ 0.0172 Ω·mm²/m
Example

A 6 mm² cable runs 20 m from the DB to a charger. Current goes out on the live and comes back on the neutral, so the loop is 40 m.

R = 0.0172 × 40 ÷ 6 = 0.115 Ω At 32 A: voltage drop = 32 × 0.115 = 3.7 V (1.6% of 230 V) Heat in cable = I²R = 32² × 0.115 = 118 W (spread over 40 m ≈ 3 W/m)

A shorter cable has less total drop and less total heat. But the heat per metre stays the same (≈ 3 W/m), so the cable runs at the same temperature. That is why a cable's current rating depends on its size, not its length.

Exercises

1. A 230 V lamp draws 0.1 A. What is its resistance?
R = V ÷ I = 230 ÷ 0.1 = 2,300 Ω
2. A 2.5 mm² cable runs 15 m one way. What is the loop resistance?
Loop = 30 m R = 0.0172 × 30 ÷ 2.5 = 0.206 Ω
Module 02 · Circuit Theory

Power & energy (kWh)

After this module: you can convert watts to amps and work out a bill from kWh.

P = V × I (DC, or AC heater-type loads) P = I² × R = V² ÷ R

Power (kW) is how fast energy is used. Energy (kWh) is power multiplied by time. Your TNB bill charges for kWh, not kW.

Energy (kWh) = Power (kW) × time (hours)
Example
3.6 kW water heater, used 30 minutes a day Current = 3,600 ÷ 230 = 15.7 A Per day = 3.6 kW × 0.5 h = 1.8 kWh Per month = 1.8 × 30 = 54 kWh
Why a faster charger doesn't raise the billA car driven 50 km a day needs about 7.5 kWh. A 7 kW charger takes about 1 hour and an 11 kW charger about 40 minutes. Both use the same 7.5 kWh.
Calculator

Monthly EV charging energy & cost

The RM/kWh rate is only an example. Use the average rate from your own TNB bill.

Exercises

1. A 1.9 kW air conditioner runs 8 hours a night. How many kWh a month?
1.9 × 8 × 30 = 456 kWh per month
2. A video claims 11 kW × 6 hours × 30 days = 1,980 kWh. Why is that unrealistic?
66 kWh a day ≈ a full battery every day (≈ 440 km). A typical driver covers 40–70 km a day → 6–11 kWh a day.
Module 03 · AC Circuits

AC & power factor

After this module: you understand what 230 V and 50 Hz mean, kW versus kVA, and power factor.

  • AC (alternating current): the current keeps reversing direction. TNB supplies 50 Hz, which is 50 cycles per second.
  • 230 V is the RMS value, the "effective average". The actual peak is 230 × √2 ≈ 325 V.
  • Single-phase homes get 230 V (live to neutral). Three phase gives 400 V between any two lives and 230 V from each live to neutral.
  • Permitted range: 230 V +10% / −6%, so 216.2 V to 253 V (per MS IEC 60038). Readings anywhere in that band are normal.

Power factor (PF)

With AC, not all of the current does useful work. Motors and compressors draw a "magnetising" current that flows back and forth without doing work.

The teh tarik analogyThe full glass is kVA, the current the cable has to carry. The tea is kW, the useful work you pay for. The froth is current that flows back and forth without doing work. PF = tea ÷ full glass. A heater has no froth (PF 1), a motor has a lot (PF ≈ 0.8), and an EV charger has almost none (PF ≈ 0.99).
kW = kVA × PF real power (what you pay for) kVA = V × I apparent power (what the cable carries) I = P ÷ (V × PF) single phase
Load typeTypical PF
Heater, kettle, water heater1.00
EV onboard charger≈ 0.99
Inverter air conditioner0.90 – 0.98
Plain motor, non-inverter air conditioner0.80 – 0.85

The cable carries the full current (kVA), so a low PF means more current for the same kW.

Exercises

1. A 2 kW motor, PF 0.8, at 230 V. What current does it draw?
I = 2,000 ÷ (230 × 0.8) = 10.9 A (at PF 1 it would be only 8.7 A)
Module 04 · Power Systems

Three phase & where √3 comes from

After this module: you can work out the current in each wire for a three-phase load.

Three phase has three live wires (L1, L2, L3). Each is 230 V to neutral, but their waveforms are 120° apart. L1, L2 and L3 reach their peaks one after another, never together.

L1 230 V L2 230 V L3 230 V 400 V 120° N
Each arrow is 230 V. The distance between the tips of L1 and L2 is 230 × √3 ≈ 400 V.

Where √3 comes from

Two 230 V arrows 120° apart. The distance between their tips comes from basic trigonometry:

V_line = 2 × 230 × sin(60°) = 230 × √3 = 230 × 1.732 ≈ 400 V

So √3 is the factor between phase voltage (live to neutral, 230 V) and line voltage (live to live, 400 V).

When to use single phase vs three phase

Single phaseThree phase
WiresL, N, E (3)L1, L2, L3, N, E (5)
Typical useMost terrace and semi-D homes, apartmentsLarge homes, shops, factories, big motors and pumps
TNB guide thresholdLoads up to about 10 kWLoads above 10 kW
Tesla home chargingUp to 7.4 kW (32 A)Up to 11 kW (16 A per phase)
CostLowerHigher: TNB application, bigger DB, more cable

Current in each wire

A balanced three-phase load shares the work equally across the three live wires. There are two ways to work it out, and both give the same answer:

Method A · divide by three
11,000 W ÷ 3 = 3,667 W per phase 3,667 ÷ (230 × 0.99) = 16.1 A

Each live wire carries about 16 A.

Method B · the √3 formula
I = P ÷ (√3 × V_line × PF) I = 11,000 ÷ (1.732 × 400 × 0.99) I = 16.0 A

This formula is just Method A written with 400 V.

Why 11,000 ÷ 400 = 27.5 A is wrong400 V is the voltage between two lives. The load isn't connected across a single pair. It has three parts, and each part gets 230 V. Dividing by 400 alone treats all the power as flowing through one wire, which overstates the current by a factor of √3.

The neutral in three phase

When all three phases are balanced, the neutral current is close to 0 A because the three currents cancel out. When they are unbalanced, the neutral carries the difference.

Example (heater loads): L1 = 20 A, L2 = 10 A, L3 = 10 A Neutral ≈ 20 − 10 = 10 A
Calculator

kW → amps per wire

Exercises

1. A single-phase Tesla charging at 7.4 kW. How many amps?
7,400 ÷ 230 = 32 A (PF ≈ 1)
2. A three-phase 10 kW air conditioner, PF 0.85, 400 V. How many amps per wire?
10,000 ÷ (1.732 × 400 × 0.85) = 17.0 A
3. Why do big houses take a three-phase supply even for the same total load?
The load is the same, but it is split across 3 wires. Each wire carries 1/3 of the current, so each phase can use a smaller cable and breaker, with less voltage drop.
Module 05 · Electrical Installation

The home supply

After this module: you know the path electricity takes from the TNB pole to your socket.

Service cableTNB
→
Cut-out / fuseTNB, sealed
→
kWh meterTNB, sealed
→
Main switchowner
→
RCCBleakage detection
→
MCBone per circuit
→
Final circuitlights, sockets, aircon, EV

Everything up to and including the meter belongs to TNB and carries a seal. Everything after the meter belongs to the owner, but wiring work must still be done by someone registered with the Energy Commission (ST). A new circuit such as an EV charger is taken from the DB, never from the meter terminals.

Wire colours

Malaysia is moving from its older British-based colour code to the international IEC 60445 code (ST Directive 11/2026). From 1 January 2029, all new wiring, upgrades and extensions must use the new code. Until then you will see both.

Old code (still common)

L1 / single-phase live: red
L2: yellow
L3: blue
Neutral: black
Earth: green/yellow

New code (IEC 60445, mandatory from 2029)

L1 / single-phase live: brown
L2: black
L3: grey
Neutral: blue
Earth: green/yellow
Black and blue swap rolesIn the old code black is neutral and blue is a live phase. In the new code black is a live phase and blue is neutral. In a house with both old and new wiring, never judge a wire by its colour. Always test it.

Typical final-circuit sizes

CircuitCopper cableTypical MCB
Lighting1.5 mm²6 – 10 A
13 A sockets (radial)2.5 mm²20 A
13 A sockets (ring)2.5 mm²32 A
Air conditioner 1 – 2 HP2.5 mm²16 – 20 A
Water heater2.5 – 4 mm²20 – 32 A
EV charger 7 kW6 mm² minimum (TNB)32 – 40 A

These are common sizes. The real size must come from the calculation in Module 07.

Module 06 · Distribution Board

Inside the DB: what each box is

After this module: you can open the DB door (only the door, not the inner cover), recognise each device, and understand what it means when one trips.

The DB (distribution board) is where the supply from the TNB meter is split into the individual circuits in the house. The drawing below shows a typical single-phase home DB. The numbers match the list below it.

from TNB meter MAIN 63A T 63A 30mA SPD T2 275V B6B10B20 B20B20B20 T C32 30mA LIGHTSLIGHTSSOCKET SOCKETAIRCONHEATEREV to earth rod 1 2 3 4 5 6 7 8 9 10
An example layout. Real DBs vary: some have no SPD, some use an RCBO for every circuit, and three-phase homes have more devices.
1

Main switch (isolator)

How to spot it: the largest device, 2-pole, marked 63A or 100A, sometimes labelled MAIN.

What it does: switches the whole house on or off. It normally does not trip by itself. Use it in an emergency or when an electrician needs to work.

2

RCCB

How to spot it: has a small button marked T (test) and is marked 30mA or 100mA.

What it does: protects people from electric shock by detecting current leaking to earth. It does not protect against overload. Details in Module 08.

3

SPD (surge protection device)

How to spot it: has small indicator windows that are green (red when worn out), marked Uc 275V, Imax 40kA, T2.

What it does: protects electronic equipment from voltage spikes. Details in Module 09.

4

MCB

How to spot it: narrow single modules marked B6, B10, C20 and so on. One MCB per circuit.

What it does: protects that circuit's cable. It trips on overload or short circuit. Details in Module 08.

5

RCBO

How to spot it: looks like an MCB but has a T button and a 30mA marking.

What it does: an MCB and an RCCB in one. Often used for dedicated circuits like an EV charger or water heater, so a leakage only trips that one circuit instead of the whole house.

6

Busbar

How to spot it: a long copper comb linking the terminals of the MCBs.

What it does: feeds every MCB from the RCCB without separate wires.

7

Neutral bar

How to spot it: the terminal block where all the neutral wires meet (black in the old code, blue in the new code).

What it does: the return path for current. Neutrals of circuits under one RCCB must go to that RCCB's own neutral bar. If they get mixed up with another group, the RCCB can trip for no obvious reason.

8

Earth bar

How to spot it: the terminal block where all the green/yellow wires meet.

What it does: connects every metal appliance body and the SPD to the earth rod.

9

Incoming cable

How to spot it: the thickest cable, coming from the TNB meter to the main switch.

What it does: carries the whole house supply. Its size limits how much load the house can draw at once.

10

Circuit labels

How to spot it: a strip or sticker under the MCBs, or a chart on the DB door.

What it does: tells you which MCB feeds what. Labels that don't match the drawings make faults hard to trace.

Real example: a three-phase 11 kW EV charger board

These photos come from a real installation: two 11 kW Tesla-type chargers, each on its own three-phase board. The wiring uses the old Malaysian colour code: L1 red, L2 yellow, L3 blue, neutral black, earth green. "Earth" and "ground" mean the same thing; ground is the American term.

L1 · red L2 · yellow L3 · blue black = N (old code)
The MCCB (main breaker for the charger) receives the three live phases on its top terminals. The black cable is the neutral in the old colour code. A 3-pole MCCB only switches the three phases; the neutral bypasses it.
N L1 L2 L3 249 / 248 / 250 V within 216–253 V ✓
A three-phase voltage and current monitor. The top row shows each phase's voltage to neutral: L1 249 V, L2 248 V, L3 250 V, all inside the permitted 216.2–253 V band. The bottom row shows current per phase; it reads 0 A because no car is charging yet. With an 11 kW charger running, each phase should read about 16 A.
N L1 L2 L3 E · green E · green
A Type 2 SPD (Schneider iPRD 40, Imax 40 kA) with one cartridge per conductor. The terminal labels printed on top read N, L1, L2, L3. The earth (green) connects at the bottom, so a surge on any phase is sent to earth. The 4-pole RCCB sits on the right.

Photos: frames from MAH BAYU ENGINEERING, "Install EV Charger 11Kw x 2" (YouTube, May 2026), used for teaching with credit. Labels added.

Reading the markings

DeviceMarkingMeaning
MCBC32Curve C, rated 32 A
MCB6000 (in a box)Breaking capacity 6 kA: can safely interrupt a short circuit of up to 6,000 A
RCCBIn 63AThe most current it can carry
RCCBIΔn 0.03ATrips at 30 mA leakage
RCCBType AC / A / BWhich kinds of leakage it can detect (Module 08)
SPDT2 · Uc 275VType 2; withstands up to 275 V continuously
SPDIn 20kA · Imax 40kAThe surge it can handle repeatedly, and the largest single surge
SPDUp 1.5kVThe highest voltage that reaches your equipment during a surge. Lower is better

When the power trips

What trippedMeaningWhat to do
One MCB onlyThat circuit is overloaded or has a shortUnplug the appliances on that circuit and switch the MCB back on. If it trips again with nothing plugged in, call an electrician
RCCB (whole house or one group dark)There is leakage somewhereSwitch off all MCBs → switch the RCCB on → switch the MCBs on one at a time. The one that trips the RCCB again is the leaking circuit. Usual suspects: water heater, outdoor socket in the rain, washing machine, water pump
SPD window redThe SPD cartridge is worn outAsk an electrician to replace the cartridge
Nothing tripped but no powerThe TNB supply may be downCheck a neighbour's house and call TNB on 15454
The T button on the RCCBPress it once a month. If it trips, it works; switch it back on. If it doesn't trip, the RCCB is faulty and must be replaced right away.

Three-phase DB: the main switch and RCCB are 4-pole (L1, L2, L3, N), there are three busbars, and there are usually three indicator lamps, one per phase. Circuits are spread across L1, L2 and L3 to keep the load balanced.

Operating the switches yourself is fine. Don't remove the inner DB cover (the one over the terminals and wires): everything behind it is live.

Module 07 · Installation Design

Cable sizing: how you know it should be 6 mm²

After this module: you can follow the steps an engineer uses to choose a cable size.

Cable heats up when current flows (I²R). PVC insulation is only good up to 70°C. Above that, the insulation slowly breaks down and can eventually catch fire. Cable sizing makes sure the cable never gets hotter than that limit and that the voltage doesn't drop too far.

Five steps

  1. Ib: design current, the current the load actually draws (Modules 03–04).
  2. In: the MCB rating. It must be In ≥ Ib. Pick a standard size: 6, 10, 16, 20, 25, 32, 40, 50, 63 A.
  3. Iz: cable capacity after correction. It must be Iz ≥ In.
    Iz = It × Ca × Cg, where It comes from the table, Ca is the temperature factor, and Cg is the factor for grouping with other circuits.
  4. Voltage drop: Vd = (mV/A/m) × Ib × L ÷ 1000. Common guideline: ≤ 3% for lighting, ≤ 5% for other loads.
  5. Fault check: make sure the MCB or RCD trips fast enough during a short circuit or earth fault. Engineers calculate this from loop impedance.

Reference table (copper, PVC 70°C, 30°C ambient)

Size1φ · B (A)1φ · C (A)3φ · B (A)3φ · C (A)1φ mV/A/m3φ mV/A/m
1.5 mm²17.519.515.517.52925
2.5 mm²242721241815
4 mm²32372832119.5
6 mm²414736417.36.4
10 mm²576550574.43.8
16 mm²768768762.82.4

B = in conduit or trunking on a wall. C = clipped directly to the wall. Figures are rounded from IEC 60364-5-52 / BS 7671 type tables for learning. Real designs must use the current standard and the manufacturer's datasheet.

Ambient temperatureCa
30°C1.00
35°C0.94
40°C0.87
45°C0.79
50°C0.71
Circuits groupedCg
1 (alone)1.00
20.80
30.70
40.65
60.57
Worked example · 7 kW EV charger
Ib = 7,000 ÷ 230 = 30.4 A In = 32 A MCB (≥ 30.4) Ambient 35°C → Ca = 0.94, alone → Cg = 1 It needed ≥ 32 ÷ 0.94 = 34.0 A Method B: 4 mm² = 32 A ✗ · 6 mm² = 41 A ✓ Voltage drop over 20 m: 7.3 × 30.4 × 20 ÷ 1000 = 4.4 V = 1.9% ✓ → 6 mm²

If the current goes even slightly above 32 A, the MCB has to step up to 40 A. Then It must be ≥ 40 ÷ 0.94 = 42.6 A, 6 mm² (41 A) no longer passes, and the cable must go up to 10 mm². That is why home chargers are usually limited to 32 A.

Cable in direct sunOutdoor cable in direct sunlight runs hotter, so Ca drops. That is why TNB's guide says to go up to 10 mm² if the EV cable is exposed to the sun.
Calculator

Choose a cable size

Exercises

1. 3.6 kW water heater, 2.5 mm² cable in conduit, 35°C ambient, 20 A MCB. Does it pass?
Ib = 3,600 ÷ 230 = 15.7 A ≤ In 20 A ✓ It needed ≥ 20 ÷ 0.94 = 21.3 A 2.5 mm² method B = 24 A ✓
2. A video says 4 mm² "can't take" a charger drawing 22.6 A. Is that right?
At 22.6 A, 4 mm² (32 A, method B) is within its rating. But the charger can be set up to 32 A, and TNB sets 6 mm² as the minimum. So the advice (use 6 mm²) is right, but not because "4 mm² can't take 22.6 A".
Module 08 · Protection

Protection: overload, short circuit, MCB, MCCB, RCCB

After this module: you know the three kinds of electrical fault, which device guards against each, and what it means when one of them trips.

Three kinds of fault

FaultWhat happensExampleDanger
OverloadCurrent somewhat above the circuit's capacity, for a long timeKettle + microwave + air fryer on one 20 A socket circuit, 28 A in totalThe cable heats slowly, the insulation degrades, and it can eventually catch fire
Short circuitLive touches neutral or another live directly. With almost no resistance, current jumps to hundreds or thousands of ampsDamaged insulation, a wire pinched by a screw, a rat chewing the cableSparks and extreme heat within milliseconds
Earth leakageCurrent leaks to earth or through a person. The current is small (mA) but enough to killA faulty water heater, a washing-machine body becomes live and someone touches itElectric shock. 30 mA and above can stop the heart

MCBs and MCCBs guard against overload and short circuit. An RCCB guards against earth leakage. An RCBO guards against all three.

MCB: how it knows when to trip

An MCB has two mechanisms inside:

  • Thermal (for overload): a bimetal strip that bends when it heats up. A small overload takes a long time to bend it far enough to trip. A larger overload bends it faster.
  • Magnetic (for short circuit): a coil. A very high current creates a strong magnetic field that pulls the trip mechanism within milliseconds.
1 hour1 min1 s0.01 s 1.13×22.6 A 1.45×29 A 5×100 A 10×200 A 20×400 A Current through a C20 MCB (multiple of In) overload: thermal short circuit: magnetic no trip
A simplified C20 MCB curve. Left of the line: no trip. Above it: trip. The higher the current, the faster it trips. In the magnetic zone (100–200 A for curve C), it trips almost instantly.
Example · C20 MCB
16 A (11 kW EV, per phase) → no trip. Normal 22 A → no trip (below 1.13 × 20 = 22.6 A) 29 A → trips within about 1 hour (1.45 × 20) 60 A → trips within a few seconds 150 A (short circuit) → trips within milliseconds

So "it trips as soon as the load goes over 20 A" isn't accurate. An MCB tolerates brief surges (a motor starting, for example) and only trips when an overload lasts long enough to heat the cable.

An MCB protects the cable, not the applianceThe MCB rating is chosen to match the cable (Module 07) so the cable never overheats. It doesn't know what is plugged in. Chargers, cars and fridges have their own internal protection.

MCB vs MCCB vs fuse

FuseMCBMCCB
Looks likeA thin wire inside a cartridgeA small DIN-rail module, 1–4 polesA large device in a hard plastic (moulded) case, screwed in place
Typical ratingAll sizesUp to 63 A (some to 125 A)16 A – 1,600 A
Breaking capacityHigh6 – 10 kA25 – 100 kA
Adjustable settingsNoNoMany models: Ir for overload, Ii for short circuit
After it operatesReplace the fuseSwitch it back onReset and switch it back on
Used forTNB cut-out, 13 A plugsFinal circuits in homesBuilding main incomers, factories, large sub-boards

Where there is an MCCB, it usually sits upstream with smaller MCBs downstream. The upstream device must be rated higher, so that when something goes wrong the MCB closest to the fault trips first and the rest of the building stays on. This principle is called discrimination (or selectivity).

The "push to trip" button on an MCCB only tests that the mechanism can trip. It doesn't test whether the MCCB will trip correctly during a real short circuit.

RCCB: how it works

  • The live and neutral both pass through a magnetic ring (toroid). Current goes out on the live and returns on the neutral, so normally their magnetic fields cancel out.
  • If current leaks to earth, less current comes back on the neutral. The ring senses the difference, and when it reaches IΔn (for example 30 mA), it trips in under 0.3 seconds.
  • An RCCB does not detect overload or a live–neutral short circuit, because the outgoing and returning currents still match. That is why it must be paired with MCBs, or replaced by RCBOs.
  • The T button creates a deliberate small leak to test the mechanism. Press it once a month.
RatingUsed for
10 mAWet areas such as a bathroom water heater
30 mAProtecting people: sockets, EV chargers
100 mAWhole-house and fire protection

The 10 / 30 / 100 mA ratings follow ST's residential wiring guideline practice. Check against the current edition.

RCD types

TypeLeakage it detectsSuitable for EV?
ACAC onlyNo
AAC + pulsating DCYes, if the charger has 6 mA DC detection (RDC-DD)
FType A + mixed frequencies (inverters)Yes, under the same condition as Type A
BEverything, including smooth DCYes, with no extra condition

IEC 60364-7-722 requires every charging point to have its own RCD, at least Type A. DC leakage of 6 mA or more can stop a Type A from working properly, so you need either 6 mA DC detection in the charger or a Type B. The Tesla Wall Connector has DC detection built in, so a 30 mA Type A is enough.

Summary: which device covers what

DeviceOverloadShort circuitEarth leakageSurge
Fuse✓✓––
MCB✓✓––
MCCB✓✓– (unless fitted with an earth-fault module)–
RCCB––✓–
RCBO✓✓✓–
SPD–––✓ (see Module 09)

MCB curves

  • Type B: magnetic trip at 3–5 × In. Standard for homes.
  • Type C: magnetic trip at 5–10 × In. For motors, compressors and EV chargers, which draw a higher starting current.
  • Type D: magnetic trip at 10–20 × In. For industrial loads such as transformers and large motors.

Exercises

1. After adding an air fryer, one socket MCB trips after 20 minutes. The RCCB doesn't trip. What's the fault?
Overload. The thermal trip takes time, and there is no leakage (the RCCB didn't trip). Move the big appliance to a different socket circuit.
2. The whole house goes dark, the RCCB has tripped, and every MCB is still ON. What's the fault?
Earth leakage on one of the circuits. Switch off all MCBs → switch on the RCCB → switch the MCBs on one at a time until you find the one that trips the RCCB.
3. Why does a 7 kW (32 A) EV charger usually use a curve C MCB rather than B?
To avoid nuisance trips from the inrush current at start-up. Curve C allows more headroom (5–10× In) before the magnetic trip.
Module 09 · Surge Protection

Surge protection (SPD)

After this module: you understand what a surge is, how an SPD protects equipment, and how an SPD differs from a lightning arrester and an RCD.

What a surge is

A surge is a voltage spike that is extremely short (microseconds, millionths of a second) but can reach thousands of volts. Common causes:

  • Lightning striking nearby, not the house itself. Its field induces a high voltage in TNB lines or phone and internet cables.
  • Switching on the TNB network, for example when TNB reroutes supply.
  • Large motors switching on and off, such as pumps or lifts in the same area.

The effect: damage to electronics such as TVs, routers, inverter aircon boards, fridges and EV chargers. Sometimes the equipment doesn't fail immediately but weakens a little each time until it dies.

01.5 kV3 kV6 kV no SPD: ~6 kV reaches equipment with SPD: limited to ~1.5 kV normal 230 V (325 V peak)
Illustration only, not a real recording. A surge lasts microseconds, so on this scale it looks like a vertical line.

How an SPD works

Inside an SPD is a component called an MOV (metal oxide varistor). It is connected in parallel: one side to live and neutral, the other side to earth.

  • At normal voltage (230 V): the MOV is like a closed door. No current flows and the SPD does nothing.
  • During a surge: once the voltage rises above its threshold, the MOV instantly conducts and dumps the surge energy to earth. The voltage reaching your equipment is limited to Up (for example 1.5 kV), which electronics can survive.
  • Analogy: the safety valve on a pressure cooker. When the pressure gets too high, the valve opens and releases the excess.

Each surge it absorbs wears the MOV a little. When it is used up, the indicator window turns red and the cartridge must be replaced.

SPD types

TypeForInstalled at
Type 1Direct lightning current entering the installation (buildings with a lightning arrester on the roof)Main DB
Type 2Induced and switching surges. The usual choice for homesHome DB
Type 3Fine protection for sensitive equipmentNext to the equipment (extension plugs with surge protection)

Specs to know

SpecMeaningTypical home value
UcMaximum continuous voltage. Must be above the supply voltage275 V
InSurge it can handle many times20 kA
ImaxLargest surge it can handle once40 kA
UpVoltage that reaches your equipment during a surge. Lower is better≤ 1.5 kV

Installing it properly

  • Keep the leads as short as possible. Surges are extremely fast, so long leads add voltage. The total lead length from busbar to SPD and SPD to earth bar should ideally be under 0.5 m.
  • Fit backup protection (a fuse or MCB ahead of the SPD). If the MOV fails short, the backup disconnects the SPD without taking out the whole house.
  • Have a good earth. The SPD sends the surge to earth, so a poor earth path reduces its effectiveness.

SPD vs lightning arrester vs RCD

ProtectsAgainst
Lightning arrester (rod on the roof + down conductor)The building structureDirect lightning strikes
SPD (in the DB)Wiring & electrical equipmentVoltage surges
RCD / RCCBPeopleElectric shock from leakage
"If there's an SPD, earth must be under 10 Ω"In ST's 2008 guideline, the 10 Ω figure is stated for lightning arrester earth electrodes and for RCD installations, not as a specific SPD requirement. A low earth resistance does help an SPD, but for an SPD, short leads and tight connections matter just as much.

For your home & EV charger

  • New developer-built homes usually already have a Type 2 SPD in the DB. Older or self-built homes may not.
  • An EV charger is expensive electronics, so a Type 2 SPD in the DB is worthwhile. Ask your installer whether your DB already has one.
  • After a thunderstorm, check the SPD indicator windows. If one is red, ask an electrician to replace the cartridge.
  • An SPD does not make equipment immune to a direct lightning strike. That needs a full lightning protection system with a Type 1 SPD.
Module 10 · Earthing

Earthing

After this module: you understand why earth resistance matters and how to test it properly.

If a live wire touches the metal body of an appliance, the earth gives that current a path to the ground. That current trips the RCD before anyone touching the body gets a shock.

Malaysian homes use the TT system: the neutral is earthed at the TNB substation, and each house has its own earth rod (usually a copper-bonded rod driven into a pit).

Touch voltage

U_touch = R_A × IΔn ≤ 50 V (IEC 60364 requirement for TT systems)
100 mA RCD → R_A ≤ 50 ÷ 0.1 = 500 Ω 30 mA RCD → R_A ≤ 50 ÷ 0.03 = 1,667 Ω

ST's guideline asks for much lower (10 Ω in the 2008 edition) so the earth stays stable all year round, including in dry spells, and suits lightning protection systems.

Calculator

Touch voltage

Testing earth properly: the 3-point method

E (earth rod) P · 62% C · ~20 m tester injects current E → C, measures voltage E → P
Disconnect the earth conductor from the rod first. Drive test stake C well away, and stake P at about 62% of that distance. Take 3 readings with P moved slightly forward and back. If they are close, use the average.
Clamp-on (stakeless) earth testersThese are convenient because no test stakes are needed. But they need a loop, meaning more than one earth path (for example a large building with many rods). On a house with a single rod, the reading can be inaccurate. For homes, the 3-point method is more reliable.

Exercises

1. Earth 161 Ω with a 100 mA RCD. What is the touch voltage? Is it safe?
161 × 0.1 = 16.1 V ≤ 50 V → meets the touch-voltage requirement. But it is still far above the 10 Ω in ST's guideline.
Module 11 · Measurement & Instrumentation

Instruments & checking cable size

After this module: you know which instrument to use, and you can check for yourself whether a cable really is 6 mm².

InstrumentUsed forTips
MultimeterVoltage, continuity, resistanceChoose one rated CAT III 600 V or higher
Clamp meterCurrent without cutting the wireClamp around one wire only. Clamping live and neutral together reads 0
Insulation tester (megger)Whether cable insulation is still soundTest at 500 V DC, minimum 1 MΩ. Supply off and loads disconnected
3-point earth testerEarth resistanceComes with test stakes and cable reels
Multifunction testerLoop impedance, RCD trip time, insulation, earthAn electrician's main tool for testing and commissioning
Socket testerWhether a socket is wired correctly (L/N/E)The safest option for non-electricians: just plug it in
Vernier caliper / micrometerDiameter of copper strands or an earth rodA micrometer is more accurate for fine strands

Checking cable size: four levels

  1. Read the print on the sheath. Genuine cable is printed with something like 6mm² 450/750V PVC IEC 60227, the brand, and a certification mark (SIRIM/ST). No print at all is a red flag.
  2. Count the strands and measure their diameter on an exposed end or an offcut. Never do this on live cable. Use the calculator below.
  3. Measure resistance per km with a low-resistance ohmmeter over a known length. IEC 60228 sets the maximum. Counterfeit cable with too little copper usually fails this test.
  4. Don't judge by outer diameter. Thick insulation doesn't mean thick copper.
SizeTypical strandsArea from strandsMax resistance @20°C (IEC 60228)
1.5 mm²7 / 0.53 mm1.54 mm²12.1 Ω/km
2.5 mm²7 / 0.67 mm2.47 mm²7.41 Ω/km
4 mm²7 / 0.85 mm3.97 mm²4.61 Ω/km
6 mm²7 / 1.04 mm5.95 mm²3.08 Ω/km
10 mm²7 / 1.35 mm10.0 mm²1.83 Ω/km
16 mm²7 / 1.70 mm15.9 mm²1.15 Ω/km
Calculator

Check cable size from strands

Calculator

Check cable size from resistance

Measure one conductor only, at room temperature. A reading at ~30°C is about 4% higher than at 20°C; the calculator corrects for that.

Earth rod

You can measure the rod diameter with a vernier caliper on the part visible in the pit (a common size is 5/8", about 16 mm). The buried length can't be measured from outside, so ask the installer for records or check the drawings. What really matters is the resistance test result in Module 10.

Module 12 · Safety & Law

Safety & the law

After this module: you know what you can do yourself and what needs a qualified person.

  • Under the Electricity Supply Act 1990 and the Electricity Regulations 1994, wiring work must be done by a competent person registered with ST (wireman, chargeman, electrical contractor).
  • Tampering with a TNB meter or its seal is an offence.
  • Safe isolation: switch off the breaker → lock it and tag it → test with a tester you have proven works → only then touch (test–prove–test).
  • You can do yourself: read cable markings, use a socket tester, press the RCD test button every month, note meter readings, and check strands on unconnected offcuts.
  • Call an electrician for: anything that needs the inner DB cover removed, connecting or replacing cables, and earth or insulation testing.