Voltage, current, resistance
After this module: you can use Ohm's Law and understand why a cable has resistance.
A water pipe is the easiest way to picture it:
| Quantity | Symbol | Unit | Water-pipe analogy |
|---|---|---|---|
| Voltage (potential difference) | V | volt (V) | Water pressure in the pipe |
| Current | I | ampere (A) | How much water flows per second |
| Resistance | R | ohm (Ω) | A narrow or partly blocked pipe |
| Power | P | watt (W) | The work the water does per second |
Ohm's Law
More pressure pushes more water through. A narrower pipe lets less water through.
Resistance of a cable
A cable has a small resistance of its own. It depends on three things: the material (copper or aluminium), the length, and the cross-sectional area (mm²).
A 6 mm² cable runs 20 m from the DB to a charger. Current goes out on the live and comes back on the neutral, so the loop is 40 m.
A shorter cable has less total drop and less total heat. But the heat per metre stays the same (≈ 3 W/m), so the cable runs at the same temperature. That is why a cable's current rating depends on its size, not its length.
Exercises
1. A 230 V lamp draws 0.1 A. What is its resistance?
2. A 2.5 mm² cable runs 15 m one way. What is the loop resistance?
Power & energy (kWh)
After this module: you can convert watts to amps and work out a bill from kWh.
Power (kW) is how fast energy is used. Energy (kWh) is power multiplied by time. Your TNB bill charges for kWh, not kW.
Monthly EV charging energy & cost
The RM/kWh rate is only an example. Use the average rate from your own TNB bill.
Exercises
1. A 1.9 kW air conditioner runs 8 hours a night. How many kWh a month?
2. A video claims 11 kW × 6 hours × 30 days = 1,980 kWh. Why is that unrealistic?
AC & power factor
After this module: you understand what 230 V and 50 Hz mean, kW versus kVA, and power factor.
- AC (alternating current): the current keeps reversing direction. TNB supplies 50 Hz, which is 50 cycles per second.
- 230 V is the RMS value, the "effective average". The actual peak is 230 × √2 ≈ 325 V.
- Single-phase homes get 230 V (live to neutral). Three phase gives 400 V between any two lives and 230 V from each live to neutral.
- Permitted range: 230 V +10% / −6%, so 216.2 V to 253 V (per MS IEC 60038). Readings anywhere in that band are normal.
Power factor (PF)
With AC, not all of the current does useful work. Motors and compressors draw a "magnetising" current that flows back and forth without doing work.
| Load type | Typical PF |
|---|---|
| Heater, kettle, water heater | 1.00 |
| EV onboard charger | ≈ 0.99 |
| Inverter air conditioner | 0.90 – 0.98 |
| Plain motor, non-inverter air conditioner | 0.80 – 0.85 |
The cable carries the full current (kVA), so a low PF means more current for the same kW.
Exercises
1. A 2 kW motor, PF 0.8, at 230 V. What current does it draw?
Three phase & where √3 comes from
After this module: you can work out the current in each wire for a three-phase load.
Three phase has three live wires (L1, L2, L3). Each is 230 V to neutral, but their waveforms are 120° apart. L1, L2 and L3 reach their peaks one after another, never together.
Where √3 comes from
Two 230 V arrows 120° apart. The distance between their tips comes from basic trigonometry:
So √3 is the factor between phase voltage (live to neutral, 230 V) and line voltage (live to live, 400 V).
When to use single phase vs three phase
| Single phase | Three phase | |
|---|---|---|
| Wires | L, N, E (3) | L1, L2, L3, N, E (5) |
| Typical use | Most terrace and semi-D homes, apartments | Large homes, shops, factories, big motors and pumps |
| TNB guide threshold | Loads up to about 10 kW | Loads above 10 kW |
| Tesla home charging | Up to 7.4 kW (32 A) | Up to 11 kW (16 A per phase) |
| Cost | Lower | Higher: TNB application, bigger DB, more cable |
Current in each wire
A balanced three-phase load shares the work equally across the three live wires. There are two ways to work it out, and both give the same answer:
Each live wire carries about 16 A.
This formula is just Method A written with 400 V.
The neutral in three phase
When all three phases are balanced, the neutral current is close to 0 A because the three currents cancel out. When they are unbalanced, the neutral carries the difference.
kW → amps per wire
Exercises
1. A single-phase Tesla charging at 7.4 kW. How many amps?
2. A three-phase 10 kW air conditioner, PF 0.85, 400 V. How many amps per wire?
3. Why do big houses take a three-phase supply even for the same total load?
The home supply
After this module: you know the path electricity takes from the TNB pole to your socket.
Everything up to and including the meter belongs to TNB and carries a seal. Everything after the meter belongs to the owner, but wiring work must still be done by someone registered with the Energy Commission (ST). A new circuit such as an EV charger is taken from the DB, never from the meter terminals.
Wire colours
Malaysia is moving from its older British-based colour code to the international IEC 60445 code (ST Directive 11/2026). From 1 January 2029, all new wiring, upgrades and extensions must use the new code. Until then you will see both.
Old code (still common)
New code (IEC 60445, mandatory from 2029)
Typical final-circuit sizes
| Circuit | Copper cable | Typical MCB |
|---|---|---|
| Lighting | 1.5 mm² | 6 – 10 A |
| 13 A sockets (radial) | 2.5 mm² | 20 A |
| 13 A sockets (ring) | 2.5 mm² | 32 A |
| Air conditioner 1 – 2 HP | 2.5 mm² | 16 – 20 A |
| Water heater | 2.5 – 4 mm² | 20 – 32 A |
| EV charger 7 kW | 6 mm² minimum (TNB) | 32 – 40 A |
These are common sizes. The real size must come from the calculation in Module 07.
Inside the DB: what each box is
After this module: you can open the DB door (only the door, not the inner cover), recognise each device, and understand what it means when one trips.
The DB (distribution board) is where the supply from the TNB meter is split into the individual circuits in the house. The drawing below shows a typical single-phase home DB. The numbers match the list below it.
Main switch (isolator)
How to spot it: the largest device, 2-pole, marked 63A or 100A, sometimes labelled MAIN.
What it does: switches the whole house on or off. It normally does not trip by itself. Use it in an emergency or when an electrician needs to work.
RCCB
How to spot it: has a small button marked T (test) and is marked 30mA or 100mA.
What it does: protects people from electric shock by detecting current leaking to earth. It does not protect against overload. Details in Module 08.
SPD (surge protection device)
How to spot it: has small indicator windows that are green (red when worn out), marked Uc 275V, Imax 40kA, T2.
What it does: protects electronic equipment from voltage spikes. Details in Module 09.
MCB
How to spot it: narrow single modules marked B6, B10, C20 and so on. One MCB per circuit.
What it does: protects that circuit's cable. It trips on overload or short circuit. Details in Module 08.
RCBO
How to spot it: looks like an MCB but has a T button and a 30mA marking.
What it does: an MCB and an RCCB in one. Often used for dedicated circuits like an EV charger or water heater, so a leakage only trips that one circuit instead of the whole house.
Busbar
How to spot it: a long copper comb linking the terminals of the MCBs.
What it does: feeds every MCB from the RCCB without separate wires.
Neutral bar
How to spot it: the terminal block where all the neutral wires meet (black in the old code, blue in the new code).
What it does: the return path for current. Neutrals of circuits under one RCCB must go to that RCCB's own neutral bar. If they get mixed up with another group, the RCCB can trip for no obvious reason.
Earth bar
How to spot it: the terminal block where all the green/yellow wires meet.
What it does: connects every metal appliance body and the SPD to the earth rod.
Incoming cable
How to spot it: the thickest cable, coming from the TNB meter to the main switch.
What it does: carries the whole house supply. Its size limits how much load the house can draw at once.
Circuit labels
How to spot it: a strip or sticker under the MCBs, or a chart on the DB door.
What it does: tells you which MCB feeds what. Labels that don't match the drawings make faults hard to trace.
Real example: a three-phase 11 kW EV charger board
These photos come from a real installation: two 11 kW Tesla-type chargers, each on its own three-phase board. The wiring uses the old Malaysian colour code: L1 red, L2 yellow, L3 blue, neutral black, earth green. "Earth" and "ground" mean the same thing; ground is the American term.
Photos: frames from MAH BAYU ENGINEERING, "Install EV Charger 11Kw x 2" (YouTube, May 2026), used for teaching with credit. Labels added.
Reading the markings
| Device | Marking | Meaning |
|---|---|---|
| MCB | C32 | Curve C, rated 32 A |
| MCB | 6000 (in a box) | Breaking capacity 6 kA: can safely interrupt a short circuit of up to 6,000 A |
| RCCB | In 63A | The most current it can carry |
| RCCB | IΔn 0.03A | Trips at 30 mA leakage |
| RCCB | Type AC / A / B | Which kinds of leakage it can detect (Module 08) |
| SPD | T2 · Uc 275V | Type 2; withstands up to 275 V continuously |
| SPD | In 20kA · Imax 40kA | The surge it can handle repeatedly, and the largest single surge |
| SPD | Up 1.5kV | The highest voltage that reaches your equipment during a surge. Lower is better |
When the power trips
| What tripped | Meaning | What to do |
|---|---|---|
| One MCB only | That circuit is overloaded or has a short | Unplug the appliances on that circuit and switch the MCB back on. If it trips again with nothing plugged in, call an electrician |
| RCCB (whole house or one group dark) | There is leakage somewhere | Switch off all MCBs → switch the RCCB on → switch the MCBs on one at a time. The one that trips the RCCB again is the leaking circuit. Usual suspects: water heater, outdoor socket in the rain, washing machine, water pump |
| SPD window red | The SPD cartridge is worn out | Ask an electrician to replace the cartridge |
| Nothing tripped but no power | The TNB supply may be down | Check a neighbour's house and call TNB on 15454 |
Three-phase DB: the main switch and RCCB are 4-pole (L1, L2, L3, N), there are three busbars, and there are usually three indicator lamps, one per phase. Circuits are spread across L1, L2 and L3 to keep the load balanced.
Operating the switches yourself is fine. Don't remove the inner DB cover (the one over the terminals and wires): everything behind it is live.
Cable sizing: how you know it should be 6 mm²
After this module: you can follow the steps an engineer uses to choose a cable size.
Cable heats up when current flows (I²R). PVC insulation is only good up to 70°C. Above that, the insulation slowly breaks down and can eventually catch fire. Cable sizing makes sure the cable never gets hotter than that limit and that the voltage doesn't drop too far.
Five steps
- Ib: design current, the current the load actually draws (Modules 03–04).
- In: the MCB rating. It must be
In ≥ Ib. Pick a standard size: 6, 10, 16, 20, 25, 32, 40, 50, 63 A. - Iz: cable capacity after correction. It must be
Iz ≥ In.Iz = It × Ca × Cg, where It comes from the table, Ca is the temperature factor, and Cg is the factor for grouping with other circuits. - Voltage drop:
Vd = (mV/A/m) × Ib × L ÷ 1000. Common guideline: ≤ 3% for lighting, ≤ 5% for other loads. - Fault check: make sure the MCB or RCD trips fast enough during a short circuit or earth fault. Engineers calculate this from loop impedance.
Reference table (copper, PVC 70°C, 30°C ambient)
| Size | 1φ · B (A) | 1φ · C (A) | 3φ · B (A) | 3φ · C (A) | 1φ mV/A/m | 3φ mV/A/m |
|---|---|---|---|---|---|---|
| 1.5 mm² | 17.5 | 19.5 | 15.5 | 17.5 | 29 | 25 |
| 2.5 mm² | 24 | 27 | 21 | 24 | 18 | 15 |
| 4 mm² | 32 | 37 | 28 | 32 | 11 | 9.5 |
| 6 mm² | 41 | 47 | 36 | 41 | 7.3 | 6.4 |
| 10 mm² | 57 | 65 | 50 | 57 | 4.4 | 3.8 |
| 16 mm² | 76 | 87 | 68 | 76 | 2.8 | 2.4 |
B = in conduit or trunking on a wall. C = clipped directly to the wall. Figures are rounded from IEC 60364-5-52 / BS 7671 type tables for learning. Real designs must use the current standard and the manufacturer's datasheet.
| Ambient temperature | Ca |
|---|---|
| 30°C | 1.00 |
| 35°C | 0.94 |
| 40°C | 0.87 |
| 45°C | 0.79 |
| 50°C | 0.71 |
| Circuits grouped | Cg |
|---|---|
| 1 (alone) | 1.00 |
| 2 | 0.80 |
| 3 | 0.70 |
| 4 | 0.65 |
| 6 | 0.57 |
If the current goes even slightly above 32 A, the MCB has to step up to 40 A. Then It must be ≥ 40 ÷ 0.94 = 42.6 A, 6 mm² (41 A) no longer passes, and the cable must go up to 10 mm². That is why home chargers are usually limited to 32 A.
Choose a cable size
Exercises
1. 3.6 kW water heater, 2.5 mm² cable in conduit, 35°C ambient, 20 A MCB. Does it pass?
2. A video says 4 mm² "can't take" a charger drawing 22.6 A. Is that right?
Protection: overload, short circuit, MCB, MCCB, RCCB
After this module: you know the three kinds of electrical fault, which device guards against each, and what it means when one of them trips.
Three kinds of fault
| Fault | What happens | Example | Danger |
|---|---|---|---|
| Overload | Current somewhat above the circuit's capacity, for a long time | Kettle + microwave + air fryer on one 20 A socket circuit, 28 A in total | The cable heats slowly, the insulation degrades, and it can eventually catch fire |
| Short circuit | Live touches neutral or another live directly. With almost no resistance, current jumps to hundreds or thousands of amps | Damaged insulation, a wire pinched by a screw, a rat chewing the cable | Sparks and extreme heat within milliseconds |
| Earth leakage | Current leaks to earth or through a person. The current is small (mA) but enough to kill | A faulty water heater, a washing-machine body becomes live and someone touches it | Electric shock. 30 mA and above can stop the heart |
MCBs and MCCBs guard against overload and short circuit. An RCCB guards against earth leakage. An RCBO guards against all three.
MCB: how it knows when to trip
An MCB has two mechanisms inside:
- Thermal (for overload): a bimetal strip that bends when it heats up. A small overload takes a long time to bend it far enough to trip. A larger overload bends it faster.
- Magnetic (for short circuit): a coil. A very high current creates a strong magnetic field that pulls the trip mechanism within milliseconds.
So "it trips as soon as the load goes over 20 A" isn't accurate. An MCB tolerates brief surges (a motor starting, for example) and only trips when an overload lasts long enough to heat the cable.
MCB vs MCCB vs fuse
| Fuse | MCB | MCCB | |
|---|---|---|---|
| Looks like | A thin wire inside a cartridge | A small DIN-rail module, 1–4 poles | A large device in a hard plastic (moulded) case, screwed in place |
| Typical rating | All sizes | Up to 63 A (some to 125 A) | 16 A – 1,600 A |
| Breaking capacity | High | 6 – 10 kA | 25 – 100 kA |
| Adjustable settings | No | No | Many models: Ir for overload, Ii for short circuit |
| After it operates | Replace the fuse | Switch it back on | Reset and switch it back on |
| Used for | TNB cut-out, 13 A plugs | Final circuits in homes | Building main incomers, factories, large sub-boards |
Where there is an MCCB, it usually sits upstream with smaller MCBs downstream. The upstream device must be rated higher, so that when something goes wrong the MCB closest to the fault trips first and the rest of the building stays on. This principle is called discrimination (or selectivity).
The "push to trip" button on an MCCB only tests that the mechanism can trip. It doesn't test whether the MCCB will trip correctly during a real short circuit.
RCCB: how it works
- The live and neutral both pass through a magnetic ring (toroid). Current goes out on the live and returns on the neutral, so normally their magnetic fields cancel out.
- If current leaks to earth, less current comes back on the neutral. The ring senses the difference, and when it reaches IΔn (for example 30 mA), it trips in under 0.3 seconds.
- An RCCB does not detect overload or a live–neutral short circuit, because the outgoing and returning currents still match. That is why it must be paired with MCBs, or replaced by RCBOs.
- The T button creates a deliberate small leak to test the mechanism. Press it once a month.
| Rating | Used for |
|---|---|
| 10 mA | Wet areas such as a bathroom water heater |
| 30 mA | Protecting people: sockets, EV chargers |
| 100 mA | Whole-house and fire protection |
The 10 / 30 / 100 mA ratings follow ST's residential wiring guideline practice. Check against the current edition.
RCD types
| Type | Leakage it detects | Suitable for EV? |
|---|---|---|
| AC | AC only | No |
| A | AC + pulsating DC | Yes, if the charger has 6 mA DC detection (RDC-DD) |
| F | Type A + mixed frequencies (inverters) | Yes, under the same condition as Type A |
| B | Everything, including smooth DC | Yes, with no extra condition |
IEC 60364-7-722 requires every charging point to have its own RCD, at least Type A. DC leakage of 6 mA or more can stop a Type A from working properly, so you need either 6 mA DC detection in the charger or a Type B. The Tesla Wall Connector has DC detection built in, so a 30 mA Type A is enough.
Summary: which device covers what
| Device | Overload | Short circuit | Earth leakage | Surge |
|---|---|---|---|---|
| Fuse | ✓ | ✓ | – | – |
| MCB | ✓ | ✓ | – | – |
| MCCB | ✓ | ✓ | – (unless fitted with an earth-fault module) | – |
| RCCB | – | – | ✓ | – |
| RCBO | ✓ | ✓ | ✓ | – |
| SPD | – | – | – | ✓ (see Module 09) |
MCB curves
- Type B: magnetic trip at 3–5 × In. Standard for homes.
- Type C: magnetic trip at 5–10 × In. For motors, compressors and EV chargers, which draw a higher starting current.
- Type D: magnetic trip at 10–20 × In. For industrial loads such as transformers and large motors.
Exercises
1. After adding an air fryer, one socket MCB trips after 20 minutes. The RCCB doesn't trip. What's the fault?
2. The whole house goes dark, the RCCB has tripped, and every MCB is still ON. What's the fault?
3. Why does a 7 kW (32 A) EV charger usually use a curve C MCB rather than B?
Surge protection (SPD)
After this module: you understand what a surge is, how an SPD protects equipment, and how an SPD differs from a lightning arrester and an RCD.
What a surge is
A surge is a voltage spike that is extremely short (microseconds, millionths of a second) but can reach thousands of volts. Common causes:
- Lightning striking nearby, not the house itself. Its field induces a high voltage in TNB lines or phone and internet cables.
- Switching on the TNB network, for example when TNB reroutes supply.
- Large motors switching on and off, such as pumps or lifts in the same area.
The effect: damage to electronics such as TVs, routers, inverter aircon boards, fridges and EV chargers. Sometimes the equipment doesn't fail immediately but weakens a little each time until it dies.
How an SPD works
Inside an SPD is a component called an MOV (metal oxide varistor). It is connected in parallel: one side to live and neutral, the other side to earth.
- At normal voltage (230 V): the MOV is like a closed door. No current flows and the SPD does nothing.
- During a surge: once the voltage rises above its threshold, the MOV instantly conducts and dumps the surge energy to earth. The voltage reaching your equipment is limited to Up (for example 1.5 kV), which electronics can survive.
- Analogy: the safety valve on a pressure cooker. When the pressure gets too high, the valve opens and releases the excess.
Each surge it absorbs wears the MOV a little. When it is used up, the indicator window turns red and the cartridge must be replaced.
SPD types
| Type | For | Installed at |
|---|---|---|
| Type 1 | Direct lightning current entering the installation (buildings with a lightning arrester on the roof) | Main DB |
| Type 2 | Induced and switching surges. The usual choice for homes | Home DB |
| Type 3 | Fine protection for sensitive equipment | Next to the equipment (extension plugs with surge protection) |
Specs to know
| Spec | Meaning | Typical home value |
|---|---|---|
| Uc | Maximum continuous voltage. Must be above the supply voltage | 275 V |
| In | Surge it can handle many times | 20 kA |
| Imax | Largest surge it can handle once | 40 kA |
| Up | Voltage that reaches your equipment during a surge. Lower is better | ≤ 1.5 kV |
Installing it properly
- Keep the leads as short as possible. Surges are extremely fast, so long leads add voltage. The total lead length from busbar to SPD and SPD to earth bar should ideally be under 0.5 m.
- Fit backup protection (a fuse or MCB ahead of the SPD). If the MOV fails short, the backup disconnects the SPD without taking out the whole house.
- Have a good earth. The SPD sends the surge to earth, so a poor earth path reduces its effectiveness.
SPD vs lightning arrester vs RCD
| Protects | Against | |
|---|---|---|
| Lightning arrester (rod on the roof + down conductor) | The building structure | Direct lightning strikes |
| SPD (in the DB) | Wiring & electrical equipment | Voltage surges |
| RCD / RCCB | People | Electric shock from leakage |
For your home & EV charger
- New developer-built homes usually already have a Type 2 SPD in the DB. Older or self-built homes may not.
- An EV charger is expensive electronics, so a Type 2 SPD in the DB is worthwhile. Ask your installer whether your DB already has one.
- After a thunderstorm, check the SPD indicator windows. If one is red, ask an electrician to replace the cartridge.
- An SPD does not make equipment immune to a direct lightning strike. That needs a full lightning protection system with a Type 1 SPD.
Earthing
After this module: you understand why earth resistance matters and how to test it properly.
If a live wire touches the metal body of an appliance, the earth gives that current a path to the ground. That current trips the RCD before anyone touching the body gets a shock.
Malaysian homes use the TT system: the neutral is earthed at the TNB substation, and each house has its own earth rod (usually a copper-bonded rod driven into a pit).
Touch voltage
ST's guideline asks for much lower (10 Ω in the 2008 edition) so the earth stays stable all year round, including in dry spells, and suits lightning protection systems.
Touch voltage
Testing earth properly: the 3-point method
Exercises
1. Earth 161 Ω with a 100 mA RCD. What is the touch voltage? Is it safe?
Instruments & checking cable size
After this module: you know which instrument to use, and you can check for yourself whether a cable really is 6 mm².
| Instrument | Used for | Tips |
|---|---|---|
| Multimeter | Voltage, continuity, resistance | Choose one rated CAT III 600 V or higher |
| Clamp meter | Current without cutting the wire | Clamp around one wire only. Clamping live and neutral together reads 0 |
| Insulation tester (megger) | Whether cable insulation is still sound | Test at 500 V DC, minimum 1 MΩ. Supply off and loads disconnected |
| 3-point earth tester | Earth resistance | Comes with test stakes and cable reels |
| Multifunction tester | Loop impedance, RCD trip time, insulation, earth | An electrician's main tool for testing and commissioning |
| Socket tester | Whether a socket is wired correctly (L/N/E) | The safest option for non-electricians: just plug it in |
| Vernier caliper / micrometer | Diameter of copper strands or an earth rod | A micrometer is more accurate for fine strands |
Checking cable size: four levels
- Read the print on the sheath. Genuine cable is printed with something like
6mm² 450/750V PVC IEC 60227, the brand, and a certification mark (SIRIM/ST). No print at all is a red flag. - Count the strands and measure their diameter on an exposed end or an offcut. Never do this on live cable. Use the calculator below.
- Measure resistance per km with a low-resistance ohmmeter over a known length. IEC 60228 sets the maximum. Counterfeit cable with too little copper usually fails this test.
- Don't judge by outer diameter. Thick insulation doesn't mean thick copper.
| Size | Typical strands | Area from strands | Max resistance @20°C (IEC 60228) |
|---|---|---|---|
| 1.5 mm² | 7 / 0.53 mm | 1.54 mm² | 12.1 Ω/km |
| 2.5 mm² | 7 / 0.67 mm | 2.47 mm² | 7.41 Ω/km |
| 4 mm² | 7 / 0.85 mm | 3.97 mm² | 4.61 Ω/km |
| 6 mm² | 7 / 1.04 mm | 5.95 mm² | 3.08 Ω/km |
| 10 mm² | 7 / 1.35 mm | 10.0 mm² | 1.83 Ω/km |
| 16 mm² | 7 / 1.70 mm | 15.9 mm² | 1.15 Ω/km |
Check cable size from strands
Check cable size from resistance
Measure one conductor only, at room temperature. A reading at ~30°C is about 4% higher than at 20°C; the calculator corrects for that.
Earth rod
You can measure the rod diameter with a vernier caliper on the part visible in the pit (a common size is 5/8", about 16 mm). The buried length can't be measured from outside, so ask the installer for records or check the drawings. What really matters is the resistance test result in Module 10.
Safety & the law
After this module: you know what you can do yourself and what needs a qualified person.
- Under the Electricity Supply Act 1990 and the Electricity Regulations 1994, wiring work must be done by a competent person registered with ST (wireman, chargeman, electrical contractor).
- Tampering with a TNB meter or its seal is an offence.
- Safe isolation: switch off the breaker → lock it and tag it → test with a tester you have proven works → only then touch (test–prove–test).
- You can do yourself: read cable markings, use a socket tester, press the RCD test button every month, note meter readings, and check strands on unconnected offcuts.
- Call an electrician for: anything that needs the inner DB cover removed, connecting or replacing cables, and earth or insulation testing.